La description

Leakage current measurement with current range from 20mA to 200A Light weight and compact design Manual range switching and auto power-off functions 24mm in diameter of measurable conductor Mean value display Auto power-off Manual range switching Approved for conformity to safety standards EN61010-1, EN61010-2-032(CAT. III 300 V)
Description Leakage Current Mini Clamp-on
Method of detection Mean Value
Display LCD (Digital display: 1999 counts)
Response Time Approx. 2 seconds
Range Switching Manual-range
Data hold On all range
Operating temperature and humidity 0 - 40°C, 85% RH or less (no condensation)
Influence of external magnetic field 10 mA or less in proximity to a 14.4 mm-dia conductor carrying 100A
Influence of conductor position Within 5 dgt for 0 to 50A, or 2% for 50 to 200A (10 mm-dia conductor at inside the jaw)
Influence of Residual Current 10 mA or less in proximity to a 10 mm-dia conductor carrying 50A
Safety Standard Conforms EN61010-1, EN61010-2-032
Circuit voltage 300 Vrms or less
Withstanding voltage 3.7 kV AC for one minute
Power Supply LR-44 x 2(3V) SR-44 x 2
Battery Life Approx. 15 hours (continuous)
Consumed current Approx. 5 mA
Auto power-off Approx. 10 minutes
Diameter of measurable conductor 24 mm at maximum
Dimensions Approx. 60 (W) x 149 (H) x 26 (D) mm
Weight Approx. 120 g
Accessories Batteries, carrying case (93033) User's manual (IM CL320)
''